Brief data for post-9D- tension post

9d- Effective area for a staggered bolted angle.

Last Updated on September 5, 2024 by Maged kamel

How do you get an Effective area for a staggered bolted angle?

In this post, I’ll discuss a solved problem involving the effective area of a staggered bolted angle. Problem 3-21: Determine the effective area of L7x4x1/2, as shown in Figure P3-21. Assume the holes are for bolts with a diameter of 1 inch.

The angle is called LLV, which stands for Long Leg Vertical. We have two lines of bolts in the long leg. The first line of bolts is 2 1/2 inches from the edge, and the gap between the two lines of bolts is 3 inches.

There is a concept of the length of connection; how do we measure it?

The first solved problem is getting an effective area for a staggered bolted angle.

In this problem, we have an equal number of bolts distributed in two rows. These bolts are staggered, and the connection length is to be from the first bolt in the first row to the last bolt in the second row.

A Solved problem for the effective area for a staggered bolted angle.

The diameter of each bolt is one inch. We need to add 1/8 inch to get the diameter of the bolt hole, which will be 1 1/8 inches.

We can get the area for L7x4x1/2 from the table; it will equal 5.26 inch2. The length of the connection will be (7*2=14 inches). The X bar distance is 0.91″.

Data for angle 7x4x1/2.

Estimation of the net area.

We will check the minimum value for the net area of the given angle by inspecting the first route line EAE, which is a vertical line passing by one hole.

The net area is the gross area minus the area of holes. In this case, the net area is equal to 4.697 inch2.

We have staggered bolts. We will check another route, E ABE’, which passes by two staggered bolts. The distance g is 3 inches, which is the vertical distance between the bolt lines, while the spacing s is the distance between bolts in the direction of the load. S equals 2 inches.

For the second route, we will add the area of the staggered path and deduct the area of holes or the area of the two holes from the gross area of the angle.

The final net area value for the second route is 4.302 inch 2, less than the net area estimated for the first route.
The final net area is the minimum of the two estimated values, 4.302 inch2.

The minimum net area estimate for the angle.

Estimation of the effective area.

We have two cases, case 2, where the shear lag factor U=1- xฬ…/ L. The value of U is equal to (1-xฬ…/L)= (1-(0.91/14)=0.935.

Case 2 for U value from table D3.1.

The second case is case 8b. When we have four or more bolts in one line, the U value is 0.80. We will select the bigger U value, which is 0.935. Multiply U by the net area; the final effective area is 4.02 inch2.

case 8 for u value

The effective area for a staggered bolted angle- the first solved problem.

The second solved problem is determining the service load capacity for a staggered bolted angle.

In this problem, we have an equal number of bolts distributed in two rows. These bolts are staggered, and the connection length is to be from the first bolt in the first row to the last bolt in the second row.

Determine the service load capacity for a staggered angle-the second solved problem.

The next slide image shows the arrangement of the bolts for the given angle. we add 1/8 inch for the bolt diameter to get the hole diameter.

data for given angle, the arrangement of bolts for the angle.

We can get the area for L6x4x1/2 from the table equal to 4.75 inch2. The length of the connection will be (7*2=14 inches). The x-bar value is 0.981 inches.

Area and x bar values for tension members.

We have two cases to consider for the connection: case 2 and case 8.

Estimation of the net area.

We will check the route E ABE’. That route passes by two staggered bolts, and the distance g is 2 1/2 inches, which is the vertical distance between the bolt lines. The spacing s is the distance between bolts in the direction of the load; S equals 2 inches.

The first route area will pass by one bolt for which the net area equals (4.75-1*1/2*1)=4.25 inch2.

The final net area value for the route is 3.95 inch2, which is less than the net area estimated from the first route.
The final net area value is the minimum of the two estimated values, 3.95 inch2.

Estimation of the effective area.

We have two cases, case 2, where the shear lag factor U=1- xฬ…/ L, we will estimate the value of U as equals (1-(0.981/14)=0.930.

The second case is case 8b. When we have four or more bolts in one line, the U value is 0.80. We will select the bigger U value, which is 0.93. Multiply U by the net area; the final effective area is 3.677 inch2.

The effective area calculations for the bolted angle.

Service load capacity and the value of Dead and live loads.

We will find the nominal load due to yielding which equals the product of gross area by the yield stress, We have ASTM-A 592, grade 50 for which the yield stress is 50ksi, while the ultimate stress is 65ksi.

The nominal load for yielding will be (4.75* 50)=237.50 kips, and the LRFD value will be (0.9* 237.50)=213.75 kips.

The nominal load due to rupture equals the product of effective area by the ultimate stress, the nominal load for rupture will be equal to (3.673*65)=238.76 kips, and the LRFD value is equal to (0.75*238.76)=179 kips.

The minimum LRFD value is 179 kips, which is the service load capacity.
We shall equate to the ultimate load; because the live load equals three times the dead load, we can calculate that the dead load is 29.80 kips and the live load is 89.40 kips.

Service load capacity for bolted angle.

The next post is post #10, about the Introduction to block shear.

There is a very useful source- introduction to Tension members.